Service Inovia Cond MAX CIRCUITO GAS Inovia Cond MAX CIRCUITO GAS
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service SCHEMA CIRCUITO GAS DIAFRAMMA VALVOLA GAS VENTILATORE SCAMBIATORE BRUCIATORE
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service VALVOLA GAS PREMIX MODELLO: SIT 848 SIGMASIT 848 SIGMA POSSIBILITA’ DI TARATURA DELLA MASSIMA QUANTITA’ DI GAS GRAZIE A INSERIMENTO VITE DI REGOLAZIONE MASSIMO GAS;POSSIBILITA’ DI TARATURA DELLA MASSIMA QUANTITA’ DI GAS GRAZIE A INSERIMENTO VITE DI REGOLAZIONE MASSIMO GAS; PRESA DI COMPENSAZIONE;PRESA DI COMPENSAZIONE; CARATTERISTICHE: AGENDO IN SENSO ORAIO SULLA VITE SI PUO’ VARIARE IL VALORE CO 2 ALLA MASSIMA POTENZAAGENDO IN SENSO ORAIO SULLA VITE SI PUO’ VARIARE IL VALORE CO 2 ALLA MASSIMA POTENZA REG. MAX
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service DIAFRAMMA GAS COMPITOCOMPITO –RIDURRE LA MASSIMA PORTATA DI GAS AL BRUCIATORE CARATTERISTICHECARATTERISTICHE –ANELLO IN OTTONE CON FORI CALIBRATI IN BASE AL TIPO DI GAS E POTENZA CALDAIA METANOGPL 25 S S
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service MIXER ARIA -AERTECH COMPITO MISCELARE L’ARIA CON IL GAS NELLE GIUSTE PROPORZIONIMISCELARE L’ARIA CON IL GAS NELLE GIUSTE PROPORZIONI RIDURRE RUMOROSITA’ BRUCIATORERIDURRE RUMOROSITA’ BRUCIATORECARATTERISTICHE SVILUPPATO PER BRUCIATORE G20 E G30/31SVILUPPATO PER BRUCIATORE G20 E G30/31 VANTAGGI NUOVO AERTECH MIGLIORATA LA FACILITA’ DI MANUTENZIONE (tenuta tubo- aertech con or + forcina acciaio);MIGLIORATA LA FACILITA’ DI MANUTENZIONE (tenuta tubo- aertech con or + forcina acciaio); MIGLIORATA SILENZIOSITA’ CALDAIAMIGLIORATA SILENZIOSITA’ CALDAIA RESTRICTOR DI MISCELAZIONE ARIA-GAS: 24 KW: COLORE FUCSIA 32 KW: COLORE BLU
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service VENTILATORE COMPITO –INVIARE AL BRUCIATORE LA MISCELA ARIA/GAS –EVACUARE I PRODOTTI DELLA COMBUSTIONE –MODULARE LA POTENZA DEL BRUCIATORE VARIANDO IL N° DI GIRI. CARATTERISTICHE – –MODELLO: EBM MRG118 – –ALIMENTAZIONE ELETTRCA: 230V ca – –POTENZA 60 W – –COLLEGATO CON 2 CABLAGGI UNO DI POTENZA E UNO DI SEGNALE ALIMENTAZIONE 230 V SEGNALE CONTROLLO NUMERO DI GIRI
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service BRUCIATORE COMPITO –PROGETTATO PER OTTIMIZZARE LA COMBUSTIONE A PREMISCELAZIONE CHE VIENE EFFETTUATA DAL SISTEMA VENTILATORE-VALVOLA GAS CARATTERISTICHE –BRUCIATORE ECOLOGICO IN ACCIAIO INOX AISI –RIDOTTE EMISSIONI INQUINANTI DI Nox (CALDAIA CLASSE 5 NOX) –FACILMENTE ESTRAIBILE DAL FRONTALE –DUE ELETTRODI MONTATI: UNO DI SCARICA E UNO DI IONIZZAZIONE –PREGETTATO PER G20 G30 G31
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service SICUREZZE TERMICHE COMPITO –EVITA SOVRATEMPERATURE IN CALDAIA O SU LATO FUMI CARATTERISTICHE –TERMOSATATO MASSIMA TEMPERATURA –TEMPERATURA DI INTERVENTO 103 °C, RIARMO AUTOMATICO –IN CASO DI INTERVENTO IL DISPLAY VISUALIZZA E02 –SONDA FUMI F1 : –PRESERVA I CONDOTTI DI ESPULSIONE –CON LA TEMPERATURA FUMI TRA I 110° C E I 120°C VIENE FORZATA LA MODULAZIONE –OLTRE I 120°C BLOCCO FIAMMA E DIAGNOSTICA LED SEGNALANO LIMITAZIONE TEMPERATURA SONDA SCARICO FUMI ( E10 ) –TERMOFUSIBILE F2: –L’INTERVENTO DI F2 INDICA UNO SCARSO SCAMBIO TERMICO –SE LA TEMPERATURA FUMI, PRIMA DI PASSARE PER LO SCAMBIATORE CONDENSANTE, SUPERA I 140° BLOCCA IMMEDIATAMENTE IL BRUCIATORE INTERROMPENDO LA SONDA FUMI ( E09) F1 SONDA FUMI F1 TERMOFUSIBILEF2 TERMOFUSIBILE F2
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service SIFONE SCARICO CONDENSA COMPITOCOMPITO –CONSENTE LO SCARICO DELLA CONDENSA ALL’ESTERNO DEL GRUPPO CONDENSANTE –EVITA CHE I FUMI POSSANO USCIRE DALLO SCARICO CONDENSA CARATTERISTICHECARATTERISTICHE –DIAMETRO RACCORDO COLLEGAMENTO: 25 mm. –TUBO DI COLLEGAMENTO: FLESSIBILE IN MATERIALE PLASTICO L= 45 cm –PALLINA INTERNA PER EVITARE FUORIUSCITE DI FUMI NEL CASO IL SIFONE SI ASCIUGHI
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service ATTIVAZIONE SPAZZACAMINO ENTRARE IN MODALITA’ SPAZZACAMINO SEGUENDO LE IDICAZIONI SOTTO RIPORTATE:ENTRARE IN MODALITA’ SPAZZACAMINO SEGUENDO LE IDICAZIONI SOTTO RIPORTATE: –CHIUDERE IL CONTATTO TA –TENERE PREMUTO I PULSANTI A+B+D IN FIGURA (CIRCA 10 sec): IL DISPLAY INDICHERA’ P01 CON IL RELATIVO VALORE IMPOSTATO –PREMERE CONTEMPORANEAMENTE I TASTI A e B ; IL DISPLAY INDICHERA’ LP + SIMBOLO SPAZZACAMINO (FUNZIONE SPAZZACAMINO ATTIVA) TARATURA VALVOLA GAS COME PER TUTTE LE CALDAIE A CONDENSAZIONE PREMISCELATE LE TARATURE DEL GAS SI ESEGUONO SOLO CON L’UTILIZZO DELL’ANALIZZATORE DI COMBUSTIONE E SEGUENDO LA PROCEDURA SOTTO INDICATA. A+B
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service REGOLAZIONE MINIMO GAS ENTRARE IN MODALITA’ SPAZZACAMINO (VEDI PAGINA PRECEDENTE) PRELEVARE ABBONDANTE ACQUA SANITARIA (IL DISPLAY DA’ LA INDICAZIONE LP OVVERO ATTIVAZIONE DELLA FUNZIONE SPAZZACAMINO MINIMA POTENZA, ALTERNATA AL VALORE DELLA TEMPERATUTRA DI MANDATA) AVVIARE ANALIZZATORE DI COMBUSTIONE CONFRONTARE IL VALORE DI CO2 LETTO CON QUELLO RIPORTATO NEL LIBRETTO A CORREDO DELLA CALDAIA (8,7% - 9,3%) AGIRE SULLA VITE INICATA IN FIGURA PER MODIFICARE IL VALORE DI CO2 ALLA MINIMA POTENZA (AVVITANDO CO2 AUMENTA) NB LA VITE DEL MINIMO E’ MOLTO SENSIBILE. AGIRE AL MASSIMO DI ¼ DI GIRO PER VOLTA ED ATTENDERE CHE IL VALORE DI CO2 LETTO SULLO STRUMENTO RIMANGA COSTANTE REG. MINIMO GAS TARATURA VALVOLA GAS
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service REGOLAZIONE MASSIMO GAS PREMERE DIVERSE VOLTE I TASTI A O B FINO A CHE IL DISPLAY NON INDICA DP ALTERNATO AL VALORE DELLA TEMPERATURA DI MANDATA (FUNZIONE FORZATURA MASSIMA POTENZA ATTIVATA) CONFRONTARE IL VALORE DI CO2 LETTO CON QUELLO RIPORTATO NEL LIBRETTO A CORREDO DELLA CALDAIA (ES. METANO 9,3% – 9,9%) AGIRE SULLA VITE INDICATA IN FIGURA PER MODIFCARE IL VALORE DI CO2 ALLA MASSIMA POTENZA (AVVITANDO CO2 DIMINUISCE) REGOLAZIONE MASSIMO GAS TARATURA VALVOLA GAS
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service TRASFORMAZIONE GAS TOGLIERE LA FORCINA “A” SVITARE IL GIRELLO “C” TOGLIERE IL TUBO “B” ESEGUIRE LA TRASFORMAZIONE DEL TIPO DI GAS SOSTITUENDO CORRETTAMENTE IL DIAFRAMMA GASMETANOGPL 25 S S
RinNOVA COND X, Inovia Cond, Inovia IN: CIRCUITO GAS Service TRASFORMAZIONE GAS ENTRARE IN MODALITA’ PROGRAMMAZIONE SCORRERE I PARAMETRI FINO A FARE APPARIRE SUL DISPLAY LCD LE LETTERE P05 MODIFICARE IL VALORE DEL PARAMETRO “5” A SECONDA DEL TIPO DI GAS CONFERMARE LA MODIFICA PREMENDO IL TASTO EFFETTUARE LE TARATURE DELLA VALVOLA GAS