MODIFICHE & INFORMAZIONI TECNICHE 2014-15
SCHEDA SIT: COMANDO + DISPLAY PRODOTTO: M160 RINNOVA COND E M260 RINNOVA CONDx ANOMALIA: LA CALDAIA FUNZIONA “A SPROPOSITO” SENZA RICHIESTA OPPURE NON RISPETTA IL SET IMPOSTATO CAUSE: IL CONTATTO CHE VIENE PORTATO SUL T.A. DELLA CALDAIA NON E’ DEL TIPO “PULITO” DATA INIZIO AGGIORNAMENTO PRODOTTO: NOVEMBRE 2013 “N…….1113” CODICE NUOVA SCHEDA COMANDO: 14064.1208.7 (BI2035 100) ETICHETTA A BORDO SCHEDA: 214_12 (e successive) NUOVA SCHEDA DISPLAY 14064.1196.2 (BI2195 113) PER RISOLVERE IL PROBELA DEVE ESSERCI L’ABBINAMENTO DELLA NUOVA SCHEDA COMANDO E NUOVO DISPLAY (+ PONTE SU SCHEDA COMANDO) MODIFICHE EFFETTUATE: AGGIORNAMENTO HW E SW SULLA SCHEDA COMANDO E DISPLAY 14064.1208.7 14064.1196.2
SCHEDA COMANDO SIT+SCHEDA DISPLAY ATTENZIONE LA SCHEDA DISPLAY 14064.1196.2 (BI2195 113) PUO’ ESSERE INSTALLATA SOLO CON LA SCHEDA COMANDO 14064.1208.7 (O VERSIONE SUPERIORE)
SCHEDA COMANDO SIT+SCHEDA DISPLAY TIPOLOGIA SCHEDA DISPLAY BI2035 101 FINO ALLA MATRICOLA N_____1013 DISPLAY BI2195 113 DALLA MATRICOLA N_____1113 CODICE 14064.1208.6 E VERSIONI PRECEDENTI FUNZIONAMENTO OK FUNZIONAMENTO NON POSSIBILE CODICE 14064.1208.7 E VERSIONI SUCCESSIVE SENZA IL PONTE (VEDI IN FOTO) CON IL PONTE (VEDI IN FOTO) VERSIONE SW PONTE CODICE SCHEDA
SCHEDA AUSILIARE SIT (INOVIA COND) PRODOTTO: M260 INOVIA COND ANOMALIA: LA CALDAIA FUNZIONA “A SPROPOSITO” SENZA RICHIESTA OPPURE NON RISPETTA IL SET IMPOSTATO CAUSE: IL CONTATTO CHE VIENE PORTATO SUL T.A. DELLA CALDAIA NON E’ “PULITO” DATA INIZIO AGGIORNAMENTO PRODOTTO: GENNAIO 2014 “N…….0114” CODICE NUOVA SCHEDA AUSILIARE: 14064.1210.1 (BI2035 120) MODIFICHE EFETTUATE: AGGIORNAMENTO HW E SW SULLA SCHEDA AUSILIARE;
SCHEDA SIT: Manutenzione Programmata PRODOTTO: M260 RINNOVA CONDx E INOVIA COND NOTE GENERALI: AGGIUNTA FUNZIONE PER AZZERARE LO STORICO DEGLI ULTIMI 10 ERRORI P08=19 (SOLO DA VERSIONE 14064.1208.7 E SUCCESSIVE); SI RICORDA CHE: INOVIA COND RINNOVA COND e CONDx INDICA CHE SONO TRASCORSI 12 MESI DALL’INSTALLAZIONE ED E’ NECESSARIO FARE LA MANUTENZIONE. PER AZZERARE LA SEGNALAZIONE METTERE P28=12 (MESI ALLA PROSSIMA MANUTENZIONE) 14064.1208.7
SCHEDE COMANDO PER CALDAIE STD: Limitazione temperatura riscaldamento PRODOTTO: BINOVA, RinNOVA, RinNOVA NOX, INOVIA, ANOMALIA: FORMAZIONE DI CONDENSA SUL PRIMARIO DOVUTO AD UN USO IMPROPRIO DELLA CALDAIA (VEDI ABBINAMENTO CON IMPIANTI A PAVIMENTO) CAUSE: TEMPERATURA DI RITORNO IMPIANTO <45°C IL CLIENTE SELEZIONA UN Tset<65°C. DATA INIZIO AGGIORNAMENTO PRODOTTO: BINOVA & IN : con introduzione scheda 14064.1220.2 (OTTOBRE 2013); RinNOVA & IN e PARVA IN : con introduzione scheda 14064.1207.5 (OTTOBRE 2013); RinNOVA NOx : con introduzione scheda 14064.1224.1 (FEBBRAIO 2014); INOVIA : con introduzione scheda 14064.1211.3 (OTTOBRE 2013); MODIFICHE EFFETTUATE: PORTATO IL VALORE DEL P27=65°C COME DEFAULT; L’UTENTE NON PUO’ SELEZIONARE UNA TEMPERATURA RISCALDAMENTO <65°C SE SI VUOLE RIPRISTINARE LA REGOLAZIONE DELLA TEMPERATURA TRA 38-85°C BISOGNA PORTARE IL P27=38°C
SCHEDE COMANDO PER CALDAIE STD: Limitazione temperatura riscaldamento PRODOTTO: BASICA, PARVA RECUPERA, PARVA RECUPERA NOX, PARVA MAX, PARVA HELIX, ARTICA, BASICA PLUS ANOMALIA: FORMAZIONE DI CONDENSA SUL PRIMARIO DOVUTO AD UN USO IMPROPRIO DEL GENERATORE (VEDI IMPIANTI A PAVIMENTO) CAUSE: TEMPERATURA DI RITORNO IMPIANTO <45°C IL CLIENTE SELEZIONA UN Tset<65°C. DATA INIZIO AGGIORNAMENTO PRODOTTO: BASICA (M97R & M290L) : con introduzione scheda di produzione 14064.1198.2 (OTTOBRE 2013) e scheda ricambio 14064.1424.1 (OTTOBRE 2013) ; BASICA PLUS (M290L) : con introduzione scheda 14064.1425.2 (OTTOBRE 2013); PARVA RECUPERA, PARVA RECUPERA Nox, PARVA MAX, PARVA HELIX, ARTICA : con introduzione scheda 14064.1195.5 (OTTOBRE 2013); MODIFICHE EFFETTUATE: PORTATO IL VALORE DEL P07=4 COME DEFAULT (=65-85°C); L’UTENTE NON PUO’ SELEZIONARE UNA TEMPERATURA RISCALDAMENTO <65°C SE SI VUOLE RIPRISTINARE LA REGOLAZIONE DELLA TEMPERATURA TRA 38-85°C BISOGNA PORTARE IL P07=1 (=38-85°C)
CALDAIE ASPIRATE: ELETTRODO ACCENSIONE PRODOTTO: RinNOVA, BASICA a CAMERA APERTA ANOMALIA: ACCENSIONI RITARDATE. CAUSE: LA SCINTILLA NON AVVIENE CORRETTAMENTE SUL BRUCIATORE; CONFORMAZIONE ELETTRODO DI ACCENSIONE; DATA INIZIO AGGIORNAMENTO PRODOTTO: INTRODOTTO NUOVO ELETTRODO CODICE 4028.6006.12/0 DI ACCENSIONE CON UNA NUOVA FORMA (VEDI FOTO); IL NUOVO ELETTRODO E’ STATO INTRODOTTO A NOVEMBRE 2013
E24: ERRORE DI COMBUSTIONE IN FASE DI ACCENSIONE PRODOTTO: BINOVA, RinNOVA, RinNOVA NOX, INOVIA,INOVIA NOX SEGNALAZIONE: LA CALDAIA IN FASE DI ACCENSIONE VA’ IN E24 = ERRORE DI COMBUSTIONE IN FASE DI ACCENSIONE. VERIFICHE CONSIGLIATE (in ordine di priorità): VERIFICARE CHE NON VI SIANO PROBLEMI DI ALIMENTAZIONE GAS (VEDI PRESSIONI GAS INSUFFICIENTI) VERIFICARE CHE IL DIAFRAMMA FUMI SIA INSTALLATO E CORRETTO IN FUNZIONE DEL TIPO E LUNGHEZZA DEL KIT FUMI; VERIFICARE LA CORRETTA TARATURA DELLA VALVOLA GAS; VERIFICARE I PARMETRI DI COMBUSTIONE (VEDI ANALISI FUMI) PER ESCLUDERE PROBLEMI DI RICIRCOLO FUMI O UNA NON CORRETTA INSTALLAZIONE DEL KIT FUMI. SOLO DOPO AVER ACCURATAMENTE VERIFICATO QUANTO SOPRA: VERIFICARE EVENTUALI PROBLEMI DELL’ELETTRODO; VERIFICARE EVENTUALI PROBLEMI DELLA SCHEDA.
ERRRORI NON PRESENTI SUL MANUALE CALDAIA PRODOTTO: BINOVA, RinNOVA, RinNOVA NOX, INOVIA,INOVIA NOX ERRORI SPORADICI IL CUI SIGNIFICATO NON E’ PRESENTE SUL MANUALE CALDAIA: E80 = SUPERATO TEMPO RICHIESTE BREVI CUMULATO. VERIFICARE CHE NON VI SIANO DELLE RICHIESTE BREVI DI TIPO SANITARIO DERIVANTI DA PROBLEMI DI PRESSIONE IDRAULICA. E81 = POSSIBILI PROBLEMI DELLA RETE ELETTRICA (DISTURBI); E82 = GUASTO INTERNO (ELETTRONICA); E83 = SPEGNIMENTO FIAMMA ENTRO POCHI SECONDI DALL’ACCENSIONE. PROBLEMI TARATURA,DI COMBUSTIONE,ELETTRODO); E84 = SUPERATO NUMERO MASSIMO DI SPEGNIMENTI FIAMMA; E85 = ERRORE INTERNO GENERICO; E86 = ERRORE INTERNO TIPICAMENTE HARDWARE O PROBLEMI DERIVANTI DALLA RETE ELETTRICA (FORMA D’ONDA ECCESSIVAMENTE DISTORTA);
SOLCONTROL (10499.0040.2) PRODOTTO: IMPLEMENTAZIONI: SOL CONTROL IN ABBINAMENTO CON BIASISOL CF HE e CF TOP IMPLEMENTAZIONI: MODIFICATO RANGE DI UTILIZZO DEI PARAMETRI P29 e P30 da 3°C a 90°C PER POTER ESEGUIRE FUNZIONI DI ANTIGELO O RICIRCOLO BOLLITORE. INTRODOTTO NUOVO SCHEMA (N°6) CHE UTILIZZA LA SONDA S2 (ANZICHE’ LA SONDA S1) PER LA GESTIONE DEI PARAMETRI P29, P30 e L’USCITA AUX1 INTRODOTTI VALORI PER IL PARAMETRO P28: P28=3 S1 PRIORITARIA; P28=4 S2 PRIORITARIA NUOVO PARAMETRO P31 PER MIGLIORARE LA GESTIONE DELLA POMPA SOLARE: P31= ΔT PER ATTIVAZIONE POMPA SOLARE TRA “TS2” E “P15” NUOVO PARAMETRO P32 PER PERMETTERE L’ATTIVAZIONE DELLA POMPA SOLARE SU P2 ANZICHE’ SU P1
REGISTRAZIONE “ACCENSIONI “CALDAIE VIA WEB V.2 Rif. circolare 003/2015 REGISTRAZIONE ACCENSIONE CALDAIA: TUTTE LE CALDAIE BIASI IMPLEMENTAZIONI: DA APRILE 2015 E’ STATO ATTIVATO IL NUOVO SISTEMA DI REGISTRAZIONE DELLE ACCENSIONI VIA WEB “Cedolini Web V.2”; VI SI ACCEDE TRAMITE IL SITO BIASI WWW.BIASI.IT ENTRANDO NELL’AREA “MONDO BIASI” E SELEZIONARE “Cedolini Web V.2”; TRAMITE LA “USER” E LA “PASSWORD” (LA STESSA DI RICAWEB) POTETE FACILMENTE REGISTRARE LE PRIME ACCENSIONI. DAL 2016 (SEGUIRA’ OPPORTUNA COMUNICAZIONE) VERRANNO ACCETATE (E CIOE’ PAGATE) SOLO E SOLTANTO LE ACCENSIONI REGISTRATE CON QUESTO SISTEMA.
ORDINI RICAMBI VIA WEB “RICAWEB” Rif. circolare 004,006 e 008/2015 SU TUTTE LE CALDAIE BIASI IMPLEMENTAZIONI: DA LUGLIO 2015 E’ STATA ATTIVATA LA PROMOZIONE ATTRAVERSO LA QUALE CHI ORDINA LE PARTI RICAMBIO VIA WEB (TRAMITE “RICAWEB”) HA DIRITTO AD UN EXTRA-SCONTO +3% SUL SUO NORMALE SCONTO. VI SI ACCEDE TRAMITE IL SITO BIASI WWW.BIASI.IT ENTRANDO NELL’AREA “MONDO BIASI” E SELEZIONARE “ORDINI RICAMBI CAT” OPPURE IN MODO DIRETTO TRAMITE IL SITO WWW.BSGCALDAIE.IT TRAMITE LA “USER” E LA “PASSWORD” POTETE NAVIGARE ALL’INTERNO DEL PORTALE ,AVERE A DISPOSIZIONE TUTTE LE TAVOLE RICAMBI DELLE CALDAIE BIASI ED INSERIRE IN MODO FACILE ED IMMEDIATO UN ORDINE RICAMBI. INOLTRE, DA OTTOBRE 2015, E’ STATA INTRODOTTA UNA NUOVA FUNZIONE CHE PERMETTE DI VISUALIZZARE LA TAVOLA RICAMBI DELLA CALDAIA INSERENDO IL NUMERO DI MATRICOLA. DAL 1°GENNAIO 2016 CHI UTILIZZERA’ IL RICAWEB AVRA’ SEMPRE DIRITTO ALL’EXTRA SCONTO 3%
NUOVA CLAUSOLA GARANZIA CONVENZIONALE Rif. circolare 010/2015 SU TUTTE LE CALDAIE BIASI PRODOTTE DA NOVEMBRE 2015 IMPLEMENTAZIONI: DA NOVEMBRE 2015 E’ STATA INSERITA ALL’INTERNO DEL CEDOLINO DI GARANZIA CONVENZIONALE UNA NUOVA CLAUSOLA CHE NE ESCLUDE LA VALIDITA’ SE IL PRODOTTO E’ STATO ACQUISTATO VIA INTERNET. La garanzia ha validità sui prodotti venduti in Italia da BSG Caldaie a Gas S.p.A. --- Via L. Biasi, 1 --- 37135 Verona. L’obbligo di BSG Caldaie a Gas S.p.A. non si estende a prodotti acquistati attraverso canali commerciali non convenzionali quali Internet per la quale sarà erogata dal venditore stesso (Codice Civile Art. 1490 e successivi) LA GARANZIA CONVENZIONALE BSG COPRIRA’ ESCLUSIVAMENTE LE VENDITE DEL CANALE TRADIZIONALE: RIVENDITORE INSTALLATORE CONSUMATORE
ERP- NUOVI CIRCOLATORI AD “ALTA EFFICIENZA” Rif. circolare 007/2015 SU TUTTE LE CALDAIE BIASI PRODOTTE DA AGOSTO 2015 IMPLEMENTAZIONI: DA AGOSTO 2015 SECONDO QUANTO STABILITO DALLA DIRETTIVA 2009/125/EU E DAL REGOLAMENTO R.EU 641/2009 TUTTE LE CALDAIE DEVONO MONTARE UN CIRCOLATORE AD ALTA EFFICIENZA (EEI<0,23 ). SONO ESCLUSI DA TALE REGOLAMENTO I CIRCOLATORI PER ACQUA POTABILE E QUELLI FORNITI COME RICAMBIO PER CALDAIE VENDUTE PRIMA DEL 01-08-2015; I NUOVI CIRCOLATORI AD ALTA EFFICIENZA HANNO DEI MOTORI SINCRONI CHE VENGONO GESTITI DA UNA SCHEDA ELETTRONICA; NON SONO DOTATI DI VITE CENTRALE PER LO SBLOCCO MA QUESTO VIENE ESEGUITO TRAMITE LA SCHEDA ELETTRONICA CHE INDUCE SUL ROTORE UN CICLO DELLA DURATA DI 5/10sec (RIPETUTO N-VOLTE) CON UNA COPPIA INCREMENTALE. NEL CASO IN CUI AL PRIMO AVVIO OPPURE DOPO UN PROLUNGATO PERIODO DI INATTIVITA’ DELLA CALDAIA IL CIRCOLATORE DOVESSE RISULTARE BLOCCATO, E’ CONSIGLIABILE FARGLI ESEGUIRE DEI CICLI DI ACCESIONE IN ASSENZA DI GAS (SUGGERIAMO N°10 cicli)
ERP- “ECODESIGN- REQUISITI PRESTAZIONALI” Rif. circolare 007/2015 APPLICAZIONE: PER TUTTE LE CALDAIE BIASI IMMESSE SUL MERCATO DAL 26-09-2015. OBBLIGHI: DAL 26 SETTEMBRE 2015 SECONDO QUANTO STABILITO DALLA DIRETTIVE 2009/125/EU E 2010/30/EU DAI REGOLAMENTI R.EU 811-812-813-814/2013 TUTTE LE CALDAIE PRODOTTE DEVONO AVERE: UN RENDIMENTO STAGIONALE DI RISCALDAMENTO D’AMBIENTE ηs ≥ 86% PER GENERATORI AVENTI Pn ≤ 70KW OPPURE η4 (rendimento al 100% del carico) ≥ 86% ed η1 (rendimento al 30% del carico) ≥ 94% p PER GENERATORI AVENTI 70KW < Pn ≤ 400KW.; UN RENDIMENTO IN SANITARIO “ηwh” (SOLO modello COMBI) MAGGIORI DEI VALORI SOTTO RIPORTATI: LE DIRETTIVE PERMETTONO COMUNQUE L’INSTALLAZIONE DI CALDAIE DEL TIPO B11 (<10KW se solo riscaldamento o <30KW se combi) COME MERA SOSTITUZIONE IN C.C.R. BASTA CHE QUESTE ABBIAMO UN RENDIMENTO STAGIONALE DI RISCALDAMENTO D’AMBIENTE ηs ≥ 75%
ERP- “ETICHETTATURA ENERGETICA DI PRODOTTO “ Rif. circolare 007/2015 APPLICAZIONE: PER TUTTE LE CALDAIE BIASI IMESSE SUL MERCATO DAL 26-09-2015. OBBLIGHI: L’ETICHETTATURA ENERGETICA DI PRODOTTO (PER GENERATORI <70KW). L’ETICHETTA VIENE MESSA A DISPOSIZIONE DAI FABBRICANTI DEGLI APPARECCHI ED E’ RESPONSABILITA’ DEI RIVENDITORI RENDERLA CHIARAMENTE VISIBILE SU CIASCUN APPARECCHIO PRESSO IL PUNTO VENDITA (SOLO DOPO IL 26-09-2015). AGLI UTENTI FINALI DOVRA’ ESSERE FORNITO UN LIVELLO DI INFORMAZIONE SUI SITI INTERNET,SUL MATERIALE PROMOZIONALE, SUI LISTINI E OFFERTE COMMERCIALI IN MODO CHIARO E PUNTUALE.
ERP- “ETICHETTATURA ENERGETICA DI SISTEMA” Rif. circolare 007/2015 APPLICAZIONE: PER TUTTI I SISTEMI BIASI(CALDAIA + DISPOSITIVI SOLARI + CONTROLLI DI TEMPERATURA) IMMESSI SUL MERCATO DAL 26-09-2015. OBBLIGHI: L’ETICHETTATURA DI SISTEMA LA CLASSIFICAZIONE ENERGETICA DI UN SISTEMA PUO’ESSERE DEFINITA SIA DAL PRODUTTORE,DA UN RIVENDITORE O DA UN INSTALLATORE CHE REALIZZA UN SISTEMA CON COMPONENTI FORNITI DA PRODUTTORI DIVERSI. IN QUESTO CASO IL SINGOLO GENERATORE A CONDENSAZIONE E’ ETICHETTATO AD ESEMPIO IN CLASSE “A” SE CONSIDERATO SEPARATAMENTE. PUO’ ARRIVARE ALLA CLASSE “A+” SE FORNITO ALL’INTERNO DI UN SISTEMA COMPRENSIVO DI CONTROLLI DI TEMEPARTURA E INTEGRAZIONE SOLARE. IL FORNITORE DEL SISTEMA, O IL RIVENDITORE CHE LO ASSEMBLA, RENDE CHIARAMENTE VISIBILI SU QUALSIASI MATERIALE PROMOZIONALE LE INFORMAZIONI RELATIVE ALLA CLASSE DELL’INTERO SISTEMA. LO STESSO SOGGETTO CHE COMMERCIALIZZA E/O METTE IN SERVIZIO E’ RESPONSABILE DI FORNIRE CONTESTUALMENTE LA SCHEDA PRODOTTO DEL SISTEMA