Scaricare la presentazione
La presentazione è in caricamento. Aspetta per favore
PubblicatoAugusto Cara Modificato 10 anni fa
1
ENERGY AUDIT on New University of Plovdiv Building - Block A Case studies work by STE Expert team in collaboration with Bulgarian EEA Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency
2
A Block A ( wing on left side ) : 1.Individual heating sub-station ( database ) 2. Utilization ( representative ) Phare twinning project BG/2004/IB/EY/01 entrata Blocco A Institutional Building at the Energy Efficiency Agency
3
Plant ground area LBA Heated floor Gross Volume Net heated Volume m²m²m²m³m³ 5.4673.1155.29322.19815.538,6 Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency
4
Phare twinning project BG/2004/IB/EY/01 1. Intonaco 2. Pannello cemento 3. Pannello pietra 1. vetro 2. camera 3. vetro 1,60 2,42 Parete verticale Vetrate Institutional Building at the Energy Efficiency Agency
5
Cornice verticale 1.ponte termico: 2.teoria delle alette 3.Keq. = 1,91 W/ mq*K Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency
6
1.Solaio cemento 2.Camera daria 3.Basamento 1.Solaio cemento 2.Camera daria 3.Isolante in fibra 4.Solaio cemento Phare twinning project BG/2004/IB/EY/01 Solaio interrato Solaio a cielo Institutional Building at the Energy Efficiency Agency
7
Phare twinning project BG/2004/IB/EY/01 LT A2 A1 A4 A3 R2R2 R s e3 R3R3 R s i3 R1R1 R s i2 R s i4 R4R4 Applicazione del modello resistivo: 1. Analoghi risultati della EEA in Mladost 2. Risultati in linea con riferimenti generali R3,A3R3,A3 R2,A2R2,A2 θeθe R1,A1R1,A1 θ si 2 θ s e1 R s e3 δ вс R s i2 R s i3 R s i1 R s e2 R s e1 θiθi θuθu Institutional Building at the Energy Efficiency Agency
8
Centrale termica: 1.Bassa temperatura entrata ( 60 °C contro i 80 °C) 1.Cattive condizioni dello scambiatore Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency
9
Radiatori: 1. Con copertura in legno si abbassa lefficienza di emissione Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency
10
Sistema di condizionamento : 1.Tipologie differenti di potenza e vetustà 2.Presenti solo in alcuni ambienti 3.( studi dei professori ) Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency
11
Sistema di illuminazione 1.Lampade a medio consumo 2.Utilizzo consistente degli apparati dato lombreggiamento degli edifici a corte Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency
12
Phare twinning project BG/2004/IB/EY/01 distribuzione dei consumi per tipologia Institutional Building at the Energy Efficiency Agency
13
Phare twinning project BG/2004/IB/EY/01 Consumi reali nel periodo 2003-2006 Institutional Building at the Energy Efficiency Agency
14
Month Average monthly temperatur e of external air Electric Energy (1) 2003-2006 Central heating Water supply Substation A consumption from D.H. network Room heating UHW (2) оСоСоСоС Day Degree М Wh BGNMWhBGNMWh BG N MWhWhMWhWhMWhWhMWhWhBGN m3m3m3m3BGN 2006 2.483297,7336.918348,0427.4956430 2003 2.551 2.551317,4539.363366,6528.9656474 2005 2.664350,5645.274394,2431.1456474 20042.416369.1451.670393,5434.6666528 Phare twinning project BG/2004/IB/EY/01 Valori medi 2003-2006 gradigiorno 2500;energia elettrica 333 MWh; termica 376 MWh Institutional Building at the Energy Efficiency Agency
15
Provincia autonoma di Bolzano Phare twinning project BG/2004/IB/EY/01 Software casaclima 1.Semplicità di confronto con altri software 2.Open source quindi confrontabile assieme a terzi ( EEA ) 3.Aggiornato su fabbisogni di raffrescamento ed energia primaria ( forma semplificata ) Institutional Building at the Energy Efficiency Agency
16
Provincia autonoma di Bolzano Phare twinning project BG/2004/IB/EY/01 Software casaclima 1.Inserimento dati dimensionali 2. dati climatici a database Institutional Building at the Energy Efficiency Agency
17
Phare twinning project BG/2004/IB/EY/01 Inserimento di 1.Tipologie costruttive 2. superfici di scambio termico Institutional Building at the Energy Efficiency Agency
18
Phare twinning project BG/2004/IB/EY/01 Inserimento di 1.Dettagli caratteristiche tecniche ( spessori- trasmittanze termiche ) Institutional Building at the Energy Efficiency Agency
19
Provincia autonoma di Bolzano Phare twinning project BG/2004/IB/EY/01 Output 1.Fabbisogni specifici 2.Potenze specifiche 3.Classificazione su protocollo casaclima ( Bolzano e località riferita )
20
Provincia autonoma di Bolzano Phare twinning project BG/2004/IB/EY/01 Input 1.Caratteristiche impianti elettrici 2.raffrescamento Correzione 1.Su dati reali i calcoli sono stati integrati Institutional Building at the Energy Efficiency Agency
21
Provincia autonoma di Bolzano Phare twinning project BG/2004/IB/EY/01 Output 1.Fabbisogni specifici 2.Potenze specifiche 3.Classificazione su protocollo casaclima ( Bolzano e località riferita ) Institutional Building at the Energy Efficiency Agency
22
Phare twinning project BG/2004/IB/EY/01 Energy Efficiency Measures Existing situation Proposed situation Savings Profitability analysis (1) Costssavings Pay- back time kWh %BGN Wall insulation (heat)683.371414.627268.77439,3138.900,0023.649,005,9 Replacement of woodwork (heat) 683.371577.615105.75615,5253.678,009.306,0027,3 TOTAL (heat)374.53054,8392.57832.95511,9 Misure correttive di efficienza energetica proposte 1 2 Institutional Building at the Energy Efficiency Agency
23
Phare twinning project BG/2004/IB/EY/01 Energy Efficiency Measures Existing situation Proposed situation Savings Profitability analysis CostssavingsPay- back time kWh %BGN Heat exch. Station refurbishing (heat) 375.600300.48075.1212025.750 6.610,003,8 Heat exch. Station refurbishing (electric) 13.14011.8561.2849,7180,00 Dismantling of radiators wooden case (heat) 165.000156.7508.25052.800 726,003,9 Thermostatic valves installation (heat) 168.000142.80025.200156.300 2.218,002,8 Lighting plant refurbishing (electric) 117.38354.05763.3265448.315 8.866,005,4 TOTAL (heat)108.571n.d. 9.554,00n.d. TOTAL (electric)64.610n.d. 9.046,00n.d. Misure correttive di efficienza energetica proposte 3 4 5 6 7 Institutional Building at the Energy Efficiency Agency
24
Phare twinning project BG/2004/IB/EY/01 Conclusioni e suggerimenti 1.Sul profilo tecnico la conoscenza e il potenziale utilizzo di più software aumentano la qualità del risultato finale riducendo la probabilità di errore umano che nel caso di raccolta ed elaborazione dati è significativo 2.Gli interventi di efficienza energetica, contestualizzati nellambito territoriale ( costi energetici della Bulgaria ) si evidenziano comunque come interessanti sul profilo economico finanziario oltre che ambientale ( isolamento a cappotto, valvole termostatiche,..) 3.La competenza in materia energetica dovrebbe essere vincolante in fase progettuale poiché ai casi come questo, concorrente alle aspettative architettoniche ( in cui la EEA è in grado di svolgere un ruolo di riferimento istituzionale ) Institutional Building at the Energy Efficiency Agency
25
Si ringraziano tutti i membri della EEA per lospitalità e la disponibilità ricevuta Phare twinning project BG/2004/IB/EY/01 Institutional Building at the Energy Efficiency Agency